SCHOOL FOR DEAF AND BLIND STEAM POWER PLANT
00033 INSTITUTE ST

Review DateStatusComment(s)
5/20/2020 E-MailI support the plan if they can comply with code for abandonment processes. Kris Cooper Deputy Fire Marshal City of Colorado Springs Fire Department 375 Printers Parkway Colorado Springs, CO 80910 TEL (719) 385-7358 Kris.cooper@coloradosprings.gov From: Manning, Stefan S. Sent: Tuesday, May 19, 2020 3:25 PM To: Cooper, Kris Cc: Smith, Steven D. Subject: Request for Underground Tank Abandonment at Colorado School for Deaf and Blind Hi Kris, I received a permit application from CGRS to abandon a tank at the Colorado School of the Deaf and Blind, and they have provided justification due to the proximity of the old foundation and the fact that the facility is on the Colorado State Register of Historic Properties. Given these factors and the proximity, I would be okay with allowing the abandonment due to the concern with damage to the historic facility with the rock foundation., especially as their proposed abandonment process meets fire code requirements for abandonment. Let me know your thoughts and if you need more information from CGRS. Thanks! STEFAN MANNING, CFPS FIRE PROTECTION ENGINEER I DIVISION OF THE FIRE MARSHAL COLORADO SPRINGS FIRE DEPARTMENT Internationally Accredited Agency, CFAI Direct: 719.385.7356 Office: 719.385.5978 Fax: 719.385.7334 stefan.manning@coloradosprings.gov
AttentionINSPECTION REQUIRED. An inspection is required prior to issuance of the permit. NOTE - EXTREMELY IMPORTANT: The inspector must observe the work being performed. In the case of underground tank installation, the inspector shall witness the installation of the tank, installation of the piping, and any pressure testing. In the case of underground tank removal, the inspector shall witness the tank inerting and removal processes. Any work that is completed without the inspector present, but requires observation, shall be deemed work without permit and assessed an additional fee. To schedule the hazardous materials inspection, please call 719-385-5978 and follow prompts to schedule the inspection. Please have the plan review number ready before calling.
FYI2015 IFC - TANKS ABANDONED IN PLACE. Tanks abandoned in place shall be as follows: 1. Flammable and combustible liquids shall be removed from the tank and connected piping. 2. The suction, inlet, gauge, vapor return and vapor lines shall be disconnected. 3. The tank shall be filled completely with an approved inert solid material. 4. Remaining underground piping shall be capped or plugged. 5. A record of tank size, location and date of abandonment shall be retained. 6. All exterior above-grade fill piping shall be permanently removed when tanks are abandoned or removed. (2015 IFC ?5704.2.13.1.4)


 