NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

RESIDENCE
06381 FARTHING DR

Review DateStatusComment(s)
5/7/2020 FYI*****(STANDARD COMMENT) This project is: Residence, 6381 Farthng Dr: new residence WUI/HS Date of Plans: 4/21/2020 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved*****(DISAPPROVED) WATER SUPPLIES To help us ensure there is adequate exterior fire protection, please provide the following: ---XXX-- Fire flow report from CSU with map (where there is no new hydrants and/or this is a an infill project. You can requestion one here: https://www.csu.org/Pages/construction-drawing-review.aspx
Disapproved*****(DISAPPROVED) INAPPROPRIATE BUILDING MATERIALS ---XXX-- Roofing materials is listed as being --DECRA OVER PLYWOOD--- where Class A Roofing materials are required PROVIDE LISTED ASSEMBLY DETAILING THIS ARRANGEMENT WITH WOOD IS A CLASS A ASSEBMLY -XXX---- Exterior cladding, soffites/eaves are listed as being -NOT SPECIFIED---- where ignition resistant material is required ---XXX-- Exterior overhangs (canti-lever areas, covered porch/deck areas) are listed as being -NOT SPECIFIED---- where ignition resistant material is required. WILL THE UNDERSIDE OF THE DECK BE ENCLOSED TO CREATE A FINISHED CEILING FOR PORCH BELOW? IF SO, YOU NEED TO IDENTIFY THESE MATERIALS, AND THEY ARE REQURIED TO BE IGNITION RESISTANT. SOFFITS - THESE WERE ALSO VAGUE - GENERAL WOOD HARDBOARD SOFFIT MATERIAL IS NOT PERMITTED. SOFFIT VENTS ARE REQUIRED TO BE COVERED WITH 1/8-INCH CREENING TO PREVENT EMBER INSTRUSION. IDENTIFY SPECIFIC MATERIAL (MANUFACTURER AND PRODUCT) YOU ARE USING.
FYI(STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) RESUBMITTALS Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dwithee@springsgov.com


 