NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

THE CLASSICAL ACADEMY NORTH ACADEMY
00975 STOUT RD

Review DateStatusComment(s)
5/18/2020 FYI*****This project is: The Classical Academy, 975 Stout Road. Addition on the north side of building. This plan review is based on the requirements found within the adopted edition of the International Building Code, International Fire Code and the related standards.
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Previous disapproval comments about construction type and building square footage were not addressed. Unable to perform a complete review until these questions are addressed.; Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYICLT REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Wyman "Chip" Taylor II, PE Fire Protection Engineer I 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7303 wyman.taylor@coloradosprings.gov
4/30/2020 FYI*****This project is: The Classical Academy, 975 Stout Road. Addition on the north side of building. This plan review is based on the requirements found within the adopted edition of the International Building Code, International Fire Code and the related standards.
FYI*****SCOPE OF WORK: relocate utilities?
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Building data shows only 27,000 sqft - is this just for the addition? our records show this building is over 100,000 sqft in size. The fire flow calculatio area is the total floor area of all floow levels eithin the exterior walls, and under the horizontal projection of the roof. Ref. B104.1 of 2015 IFC. 2. Our records show this building to be of II-A construction. Your plans are placing it at I-B - verify construction type and correct if needed. 3. provide an exhibit showing the entire site, clearly delineating the expansion, existing hydrants etc. the addition could be iimpacting the entire fire hydrant requirements - number and spacing as well as fire flow. How do we know if there is enought hydrfants, compliance spacing and fire flow for the addition? Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYICORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYIREVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYIDEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dee.withee@coloradosprings.gov


 