NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

ENT FEDERAL CREDIT UNION
07250 CAMPUS DR

Review DateStatusComment(s)
5/13/2020 FYI*****(STANDARD COMMENT) This project is: ENT Headquarters Data Room, 7250 Campus Dr, Fixed Fire - Clean Agent Fire Suppression and Pre-action System for Data Room This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Show supervisory signal in sequence of operation for removal of electric actuator per NFPA 2001, 4.3.4.2. 2. Show supervisory signal in sequence of operation for high and low pressure on pre-action sprinkler system per NFPA 72, 17.17.2 3. Provide cut sheets for pipe hangers and hanger attachments to be used. 4. You must provide a completed permit application form with your submittal. 5. RME must sign all pages of the plans and the coversheet of the cut sheets. 6. Is pre-action system located in the same room as the clean agent system? 7. Provide documentation that the room enclose meets the structural strength requirements for the system being provided per NFPA 2001, Appendix D 8. Provide detector above new releasing panel. 9. Change system activation strobe outside room to a red lens. 10. Cut sheets still not provided for all devices documenting current draws shown in battery calculations 11. Why are you only showing alarm current draw for 2 detectors when there are 6 being added? 12. Clarify how you arrived at total alarm and supervisory current draws. Total current draws shown in calculations do not added up to the amounts shown. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
Attention(STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) CLT REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Wyman "Chip" Taylor II, PE Fire Protection Engineer I 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7303/(F) 719-385-7330 wtaylor@springsgov.com
4/13/2020 FYI*****(STANDARD COMMENT) This project is: ENT Headquarters Data Room, 7250 Campus Dr, Fixed Fire - Clean Agent Fire Suppression for Data Room This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Please review ALL cut/data sheets. It appears that not all cut/data sheets are provided. In addition all current draws used in battery clacs shall be highlighted for ease of reference and etc.. 2. Plans indicate that this releasing system will activate and also monitor a pre-action system, however the sequence of operation does not indicate what will activate the pre-action system. In addition provide in your scope of work whether this was an existing or new pre-action system. 3. Correct edition of NFPA 72 standard on cover sheet to indicate 2019 NFPA 72, not 2015. There was never a 2015 NFPA 72. 4. Correct tank size on Sheet 4. 5. Provide CSFD PR# 2020-0527-FF-1 on re-submittal. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
Attention(STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI*****(STANDARD COMMENT 24) DISAPPROVED ITEMS ADDRESSED: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether of not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) JAH REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Jeff Hanenberg Senior Fire Code Inspector 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7359 / (F) 719-385-7330 jeff.hanenberg@coloradosprings.gov


 