NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

MOUNTAIN VIEW ACADEMY
02103 MEADOWBROOK PKWY

Review DateStatusComment(s)
5/11/2020 FYI*****(STANDARD COMMENT) This project is: Mountain View Academy, 2103 Meadowbrook Py: new elementary school. You can access our web site for the latest fire department plan review comments: www.coloradosprings.gov search for Plan and Construction Review.
Disapproved*****(STANDARD COMMENT 19) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: OUTSTANDING COMMENTS FROM PREVIOUS REVIEW: 1. Heat in water entry room - this is not clearly identified on the mechanical drawings. indicate a unit heater and/or provide written explanation heat is provided in the water entry room (fire entry/fire riser). 2. Water supply approval from Falcon Fire - you provided a letter from Falcon Fire where they reviewed and approved the site access. This letter explicitly states there was no review for the water supplies and directs you to submit for view a separate water plan. CSFD cannot move forward with approval of building plans without knowing there is adequate water supply available. 3. Flow tests for hydrants were provided, dated January 2020: unfortunately, there is nothing provided to connect the tested hydrants to this site. Provide a site plan showing the location of these hydrants in relation to the site. 4. No indication of any fire department connection was noted. PLEASE NOTE: You are to provide a written response on letterhead to disapproval comments. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYI(STANDARD COMMENT) RESUBMITTALS Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
FYI*****(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. Occupant load: reviewer calculated total occupant load to be 1862 2. Address assignment provided.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dwithee@springsgov.com
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
4/7/2020 FYI*****(STANDARD COMMENT) This project is: Mountain View Elementary, 2103 Meadowbrook Py: new elementary school. You can access our web site for the latest fire department plan review comments: www.coloradosprings.gov search for Plan and Construction Review.
FYI*****(STANDARD COMMENT) DELEGATED PROJECTS The review and inspection of this plan set and permit has been delegated to the CSFD by ---FALCON -- Fire Protection District through a Memorandum of Understanding. Be Advised CSFD does not review delegated projects for site access or water supplies.
FYI*****(STANDARD COMMENT) BUILDING DATA: Size of Bldg. ---42150-- sq ft Construction Type ---V-B--- Fire Sprinklers Y-XXX---- Required GPM: -2750--- gpm Minimum # of hydrant(s) required: ---3-- Max AVG spacing between hydrants: -450---- ft Max hose lay: --225 ft
Disapproved*****(STANDARD COMMENT 19) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Provide the total occupant load of the building. 2. I did not see where there is heat within the water entry/fire riser room. Please verify and call out this is provided. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Disapproved*****(DISAPROVED) DELEGATED PROJECTS: Provide documentation of water supply approvals by --FALCON--- Fire Protection District. FIRE LINE IS ACCEPTABLE MATERIAL PER FIRE DEPARTMENT REGULATIONS. HAVE FALCON FIRE APPROVE FIRE HYDRANT LOCATIONS. ALSO PROVIDE MODELED FIRE FLOWS FOR NEW HYDRANTS AND/OR FIRE FLOW REPORTS DATED WITHIN 5 YEARS FROM EXISTING HYDRANTS ALONG THIS MAIN. SHOW LOCATION OF FIRE DEPARTMENT CONNECTION - ENSURE IT IS WITHIN 100 FEET OF A FIRE HYDRANT AND ALONG FRONT OF THE BUILDING.
Disapproved(DISAPPROVED) TEMPORARY ADDRESS PLEASE PROVIDE DOCUMENTATION THE ADDRESS YOU ARE USING IS THE ASSIGNED AND APPROVED ADDRESS FOR THIS LOT.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYI(STANDARD COMMENT) RESUBMITTALS Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dwithee@springsgov.com
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.


 