5/12/2020 FYI*****This project is: Revel Crossing at Wolf Ranch Filing 1. Located northwest of Wolf Valley Drive and Research Parkway. This plan review is based on the requirements found within the adopted edition of the International Building Code, International Fire Code and the related standards.
FYI*****SCOPE OF WORK: main extension with fire hydrants for subdivision
Attention(STANDARD COMMENT) READY FOR SIGNATURES: The water plans appear ready for signature. Please provide one hard copy for CSFD records along with your final copies for our signature. Be sure you have addressed any red-lined comments.
FYI*****RED-LINED COMMENTS The following RED-LINED items are to be corrected prior to signature and/or final inspection: 1. Noted hydrant can be eliminated due to proximity of existing hydrant across the street 2. It is recommended that a hydrant be added as noted.
Attention***** 2015 IFC B105 FIRE FLOW REQUIREMENT: Size of Bldg. ---4000-- sq ft Construction Type --1750---- Fire Sprinklers N--xxx--- Required GPM: --1750--- gpm Minimum # of hydrant(s) required: --1--- Max AVG spacing between hydrants: --500--- ft Max hose lay: --250--- ft
FYI*****FIRE FLOW/HYDRANT REQUIREMENTS MET: On this site fire flows are -3700--- gpm, and the numbers of hydrant(s) are -ACCEPTABLE--- based on a THEORETICAL Report. This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure.
FYI2015 IFC TABLE C105.2 HYDRANT PAINTING REQUIREMENT: Fire hydrants shall be painted in compliance with the adopted fire code. By using this scheme, emergency response crews are provided a quick way to decipher how much water is available.
FYIREVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYIDEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dee.withee@coloradosprings.gov


 