PRIVATE RESIDENCE
03930 STAR RISE PT

Review DateStatusComment(s)
4/7/2020 FYI*****(STANDARD COMMENT) This project is: Private Residence, 3930 Star Rise Pt: WUI home, non hillside Date of Plans: 2.5.2020 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI2015 IFC 3310 ACCESS FOR FIREFIGHTING Approved vehicle access for firefighing shall be provided to all construction/demolition sites. Vehicle access shall be either temporary or permanent roads, capable of supporting vehicle loading under all weather conditions. Vehicle access shall be maintained until permanent fire apparatus access roads are available.
FYI2015 IFC 503.2.7 WUI DRIVEWAYS Zoning Code ?7.3.504.D.2.d.(2)(A)(ii) When driveways serve as a fire department access road, the width shall be a minimum of twelve feet (12-ft) and having a slope of twelve percent (12%) or less. WUI GRADE (Hillside Standards as identified in the Public Works Design Manual for Hillside Development) The absolute maximum street grade allowed is 12%. The maximum run for the 12% grade is 250-feet.
FYI2015 IFC 503.2.3 SURFACE Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all weather driving capabilities.
FYI2015 IFC 503.2.3 LOADING D102.1 as amended Fire apparatus access roads shall be designed, constructed and maintained to support the imposed loads of fire apparatus weighing at least 75,000lbs. with a minimum single axle weight of 27,000lbs.
FYI2015 IFC 503.1.1 150-FOOT ACCESS Fire apparatus access roads shall be provided for every structure constructed or moved into or within the jurisdiction and shall be extended to within 150-feet of all exterior portions of the first story of any building. Exception: Where there are not more than 2 Group R3 or U occupancies
FYI2015 IFC 505.1; 2017 RBC 312 ADDRESSING: Address shall be posted on street addressed side of structure. Minimum 5" numbers with 1/2" stroke. Contrasting color to background.
FYI(STANDARD COMMENT) INCREASED WILDFIRE RISK. Residing in or near the wildland-urban interface areas involves increased fire risks that may not apply in urban or more urbanized types of developed communities.
FYI*****(STANDARD COMMENT) ACCEPTED CONSTRUCTION MATERIALS/METHODS Roofing materials is listed as being ---Tile-- meeting the Class A requirements of Regional Building Code 303.4.61.1 Decking material is listed as being --Trex--- meeting the requirements for ignition resistant construction. Exterior cladding, is listed as being --Stucco--- meeting the requirements for ignition resistant construction. Soffit/Eaves is listed as being ---Cement Hardie Board-- meeting the requirements for ignition resistant construction. Exterior overhangs (canti-lever areas, covered porch/deck ceilings) are listed as being --Stucco--- meeting the requirements for ignition resistant construction. ---X-- Attic is shown a conditioned attic, as such there are no vents for the attic. (See also the Amended 2015 International Fire Code Appendix K Section K104 for hardened structure requirements.)
FYI(STANDARD COMMENT) HILLSIDE ORDINANCE This lot/development is subject to the requirements of section of 20-4-10 5 CE (2) (Ordinances 93-48 and 93-49) of the City Code establishing minimum safety criteria for residential construction in the City's Hillside Areas. Ensure all landscaping complies with the wildfire interface specifications as required by the fire department and zoning/planning departments.
FYI(STANDARD COMMENT) SOC RESPONSE TIMES Fire service response times to this area do not fall within the CSFD interim Standard of Response Coverage. The CSFD is unable to provide the following level of service: - 90% of all emergencies reached within 8 minutes (first due company) - 90% of structure fires requiring a full effective fire-fighting complement (2 engine companies, 1 ladder/truck company) within 12 minutes.
Attention2015 IFC K102 FUELS MANAGEMENT SAFETY ZONE: Brush patches or clusters may be left in the safety zone, but shall be separated by clear areas of 10-feet or more of noncombustible materials or grass mowed to not more than 4-inches in height. CLEARANCE TO MAIN STRUCTURE: No hazardous brush, trees or shrubs shall be allowed within 15-feet of the main structure or significant accessory structure such as sheds, decks and pergolas. The trunks of deciduous trees may be allowed to be planted as close as 10-feet from structures where approved by the Fire Code Official. Small brush patches not exceeding 100-square feet in size or trees no larger than 15 linear feet in any direction may be allowed to encroach into this zone. PRUNING OF LIMBS: Large trees shall not be allowed to have limbs overlap smaller trees or brush, and shall be pruned of dead limbs to a height up to 10-feet while maintaining a minimum 70% of the tree's crown. Certain tree clusters may be permitted if sufficient clear area is provided and approved by the Fire Code Official. CLEARANCE OF TREE BRANCHES TO STRUCTURES OR APPURTENANCES: Character tree branches shall not extend over or under the roof or eaves, and the canopy or drip-line shall not be within 15-feet of a deck or similar combustible projection, wood burning appliance or chimney unless approved by the Fire Code Official. For additional information concerning this issue - contact our Wildfire Mitigation Administrator at 385-7368 or https://coloradosprings.gov/fire-department/page/wildfire-mitigation-0?mlid=9906
FYI(STANDARD COMMENT) CLASS A ROOFING A Class A roof covering (excluding solid wood roofing products) shall be installed on all Residential Occupancies and a minimum Class B roof covering shall be installed on all remaining occupancies (Not to replace Class A where already required by Table 15-A) at the time an application is made for a roofing or re-roofing building permit within the limits of the City of Colorado Springs, Colorado.
Attention2015 IFC K104 IGNITION-RESISTANT CONSTRUCTION REQUIREMENTS 1. Exterior cladding, eaves and soffits shall be constructed of ignition resistant materials, including but not limited to: fiber-cement board, stucco, masonry/brick, manufactured stone and similar materials. Natural wood/cedar siding, hardboard, vinyl and similar combustibles are not permitted. Natural wood or plastic products used for fascia, trim board materials and trim accents are allowed when painted or as approved. 2. For any portion of the attached structure with projections or overhangs, the area below shall have all horizontal under-floor areas enclosed with ignition resistive materials such as allowed in item 1 above. 3. Exterior doors shall be noncombustible or solid core not less than 1 3/4-inches thick. Windows within doors and glazed doors shall be tempered safety glass or multi-layered glazed panels. 4. Exterior windows shall be a minimum double pane. Tempered panes are preferable but not required. 5. All attic vents shall be screen with wire mesh or hardware cloth having openings no larger than 1/8-inch. Soffit vents are permitted, gable vents may be allowed as approved by the Fire Code Official. 6. Gutters and downspouts of non-combustible construction shall be installed such that the leading edge of the roof is finished with a metal drip edge so that no wood sheathing is exposed. Drip edge shall extend into the gutter. Vinyl gutters may be allowed but must have a noncombustible landing area below the roof line, a minimum of 5-feet from the side of the structure/foundation. Gutter caps are strongly recommended to prevent accumulation of combustible debris in the gutters. 7. Decks and other habitable spaces shall be of ignition resistant or non-combustible decking materials, such as metal or composite materials. Wood is permitted for use for large structural components and railings (ie vertical members). 8. The base of exterior walls, posts or columns shall be protected on the bottom side with provision such as fire resistant foam or wire mesh having openings no larger than 1/8-inch. 9. Chimneys serving fireplaces, and other solid or liquid fueled heating appliances shall have an approved spark arrestor or cap.
Attention(STANDARD COMMENT) CONSTRUCTION PERMIT REVIEW REQUIREMENTS: Plans for any structure lying within the WUI Overlay area must be approved by the Colorado Springs Fire Department Construction Services prior to issuance of a building permit. Final approval by CSFD on all permits issued by RBD is required prior to issuance of the Certificate of Occupancy.
FYI*****(STANDARD COMMENT) FIRE FLOW REQUIREMENT: Size of Bldg. ---6904-- sq ft Construction Type --VB---- Fire Sprinklers Y----- N--X--- Fire Walls Y ----- N --X--- Required GPM: --2250--- gpm # of hydrant(s) required: -2---- Max AVG spacing between hydrants: --450--- ft Max hose lay: ---225-- ft
FYI*****(STANDARD COMMENT) FIRE FLOW/HYDRANT REQUIREMENTS MET: On this site fire flows are --3442-- gpm, and the numbers of hydrant(s) are --Adequate-- based on an ACTUAL Report. This site, based upon the provided theoretical modeled fire flows, appear to meet the minimum flow requirements and/or the number of hydrant(s) for this structure.
FYI(STANDARD COMMENT) WATER SUPPLY REQUIRED ON SITE: 2015 IFC 3312 Required water supplies for fire protection, either temporary or permanent, shall be made available as soon as combustible material arrives on the site. It is the responsibility of th owner or their designated representative to ensure an approved water supply is provided.
FYI*****(STANDARD COMMENT) SCHEDULING INSPECTIONS Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. You will need to schedule an inspection at the time of Framing and a final inspection at completion. Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 2013-1234 - HS-1) The CSFD Approved sets of plans are to be on site for all inspections.
FYI*****(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. An actual fire flow test was conducted on 03/30/20 and produced 3442 GPM @ 20 PSI from Hydrant 1666-C, closest hydrant to home.
FYI(STANDARD COMMENT) PERMITS Insure all applicable permits are obtained from the Regional Building Department and the Colorado Springs Fire Department for the work that is being done at this site.
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYI(STANDARD COMMENT) JAH REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Jeff Hanenberg Senior Fire Code Inspector 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7359 jeff.hanenberg@coloradosprings.gov
3/24/2020 FYI*****(STANDARD COMMENT) This project is: Private Residence, 3930 Star Rise Pt: WUI home, non hillside Date of Plans: 2.5.2020 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved(DISAPPROVED) INSUFFICIENT WATER/HYDRANTS The available fire flows and/or number of hydrants at this location, do not meet the fire code requirements. You have several options: 1) Reduce the Square Footage 2) Install a 2-hour Fire Wall (openings are not permitted) 3) Install additional fire hydrants (provided adequate fire flows are available) 4) Install a fire sprinkler system. (You can get a 50% reduction in required fire flows if you install an approved fire sprinkler system.) 5) Request a simultaneous fire flow report if this has not already been done 6) Change the construction type 7) Request actual fire flow test NEAREST HYDRANT, 1666-C PRODUCES ONLY 1300 GPM
FYI(STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) RESUBMITTALS Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYI(STANDARD COMMENT) RTP REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Roland Peterson Senior Fire Inspector, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7369 rpeterson@springsgov.com
3/16/2020 FYI*****(STANDARD COMMENT) This project is: Private Residence, 3930 Star Rise Pt: WUI home, non hillside Date of Plans: 2.5.2020 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved*****(DISAPPROVED) WATER SUPPLIES To help us ensure there is adequate exterior fire protection, please provide the following: ---X-- Fire flow report from CSU with map (where there is no new hydrants and/or this is a an infill project. You can requestion one here: https://www.csu.org/Pages/construction-drawing-review.aspx
FYI(STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) RESUBMITTALS Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYI*****(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED The plans have been resubmitted and SOME of the disapproved comments have been addressed and/or corrected as follows: -XXX---- Decking material is listed as being ---NOT SPECIFIED-- where ignition resistant material is required NOW LISTED AS TREX NOTE: COVERED DECK CEILING WAS NOTED TO BE OF CEMENTITIOUS MATERIAL - REVIEWER ASSUMES COVERED ENTRY IS OF SAME MATERIALS FOR CONSISTENCY. NOW NOTED AS STUCCO
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYI(STANDARD COMMENT) JAH REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Jeff Hanenberg Senior Fire Code Inspector 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7359 jeff.hanenberg@coloradosprings.gov
2/25/2020 FYI*****(STANDARD COMMENT) This project is: Private Residence, 3930 Star Rise Pt: WUI home, non hillside Date of Plans: 2.5.2020 This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved*****(DISAPPROVED) INAPPROPRIATE BUILDING MATERIALS -XXX---- Decking material is listed as being ---NOT SPECIFIED-- where ignition resistant material is required NOTE: COVERED DECK CEILING WAS NOTED TO BE OF CEMENTITIOUS MATERIAL - REVIEWER ASSUMES COVERED ENTRY IS OF SAME MATERIALS FOR CONSISTENCY.
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dwithee@springsgov.com


 