NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

O REILLY AUTO PARTS
02417 MARKSHEFFEL RD

Review DateStatusComment(s)
2/26/2020 AttentionEXCEEDS PERMIT QUANTITIES; ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT REQUIRED. COLLECT REQUIRED INFORMATION FOR ANNUAL PERMITTING.
FYICHEMICAL INVENTORY, AS DECLARED Various automotive repair chemicals - see HMIS provided with plans for exact chemicals. Aerosols, Level 1 - 331.57 lbs Aersols, Level 2 - 125.56 lbs Aerosols, Level 3 - 618.22 lbs Combination 2/3 total - 743 lbs (2,500 lbs MAQ per Table 5104.3.1) Flammable Liquids IB - 83.85 gal IC - 209.14 gal Combustible Liquids II - 83.79 gal IIA - 33.21 gal Combined (IB through IIIA) - 702 gal (7,500 gal MAQ per Table 5704.3.4.1) IIIB - 2117.37 gal (no MAQ per Table 5704.3.4.1) Corrosive liquids 210.94 gal (1000 gal MAQ per Table 5003.1.1(2)) Oxidizing liquids Class 1 - 1.69 gal (800 gal MAQ per Table 5003.1.1(1)) Water Reactive Class 1 - 0.12 gal (No MAQ per Table 5003.1.1(1)) Class 2 - 94.49 gal ( MAQ of 10 gal per Table 5003.1.1(1))
DisapprovedProvide specification sheets on Oil tank and Gravity Feed Oil Rack and answer the following comments: 1. How is the tank being filled? Is it filled on site or will it be replaced with a new tank? 2. How will the oil tank be vented? Is it vented outside or will it be vented inside (if vented inside a pressure-vacuum vent cap is required) 3. How will oil tank be feeding the oil rack? 4. What are the secondary containment methods?
DisapprovedTHE CHEMICAL INVENTORY, AS DECLARED, EXCEEDS THE ALLOWABLE THRESHOLDS FOR WATER REACTIVE CLASS 2, AS DEFINED BY 2015 IFC TABLE 5003.1.1(1) AND/OR 5003.1.1(2). YOU WILL BE REQUIRED TO RESUBMIT YOUR PLANS TO THE PPRBD FOR A RE-CLASSIFICATION OF THE OCCUPANCY TYPE IN WHICH THIS/THESE CHEMICAL TYPE(S) ARE USED AND/OR STORED, TO AN H3 PER THESE TABLES. Total amount of Water Reactive Class 2 proposed - 95 gal; MAQ is 50 lbs x 2 = 100 lbs, or about 10 gal. Note that the Water Reactive Class 2 chemicals in the HMIS are lead acid batteries - please verify that these batteries do in fact meet the definition of a Water Reactive Class 2 per the IFC. Verify and correct.
FYICONTROL AREAS, AS SHOWN ON THIS SUBMITTAL ARE AS FOLLOWS Entire Building


 