NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

O REILLY AUTO PARTS
02417 MARKSHEFFEL RD

Review DateStatusComment(s)
2/19/2020 FYI*****(STANDARD COMMENT) This project is: O Reillys Auto Parts, 2417 Marksheffel Rde: new auto parts retail facility Date of Plans: 1.17.2020 You can access our web site for the latest fire department plan review comments: www.coloradosprings.gov search for Plan and Construction Review.
FYI*****(STANDARD COMMENT) DELEGATED PROJECTS The review and inspection of this plan set and permit has been delegated to the CSFD by ---FALCON-- Fire Protection District through a Memorandum of Understanding. Be Advised CSFD does not review delegated projects for site access or water supplies (hydrants).
Disapproved*****(STANDARD COMMENT 19) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Provide details on shelving - height of the top of storage, for Class I-IV and high hazard materials identified in the HMIS submittal. 2. Provide fire flow information for existing fire hydrant. ( IFC 507.1) 3. Utility plans (fire line): Identify the material of the fire line. Provide the thrust block details and calculations per NFPA 13. Detail A4.2 of CSU standards does nto provided for 90 degree bends. Verify composition of thrust block complies or exceeds NFPA requirements as follows: 1 part cement, 2.5 parts sand, 5 parts stone. NOTE it is recommended that 90 degree bends be avoided in fire lines. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Disapproved*****(DISAPROVED) DELEGATED PROJECTS: Provide documentation of site plan and water supply approvals by ---FALCON-- Fire Protection District. Falcon Fire Protection District shall be consulted regarding site access and external fire protection (fire hydrant - location and access to) and documentation of their approval shall be provided in the resubmittal of the construction documents. CSFD will review and inspect all fire lines.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
FYI(STANDARD COMMENT) RESUBMITTALS Re-reviews may be submitted back to the CSFD by direct submittal at the Construction Services counter, or through the Regional Building Department's routing system.
FYI(STANDARD COMMENT) DEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dwithee@springsgov.com
FYI(STANDARD COMMENT) REVIEWS: 2015 IFC 105.4.4 Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code.


 