NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

BMC LUMBER SUITE 1805
01805 ACADEMY BLVD

Review DateStatusComment(s)
2/18/2020 DisapprovedCurrent Occupancy Classification is B/S-1/M per C80615; however, this plan indicates woodworking/millwork which would require an F-1 occupancy classification. Please provide documentation from PPRBD that either the current occupancy classification is correct or a Change of Occupany will be required.
DisapprovedPlease provide particulate hazard determination in accordance with 2017 NFPA 664 8.2.1 through 8.2.1.5. No risk assessment has been submitted; please provide a risk assessment to determine whether a fire hazard, deflagration hazard, or both, exist in this system.
DisapprovedPlease verify if the planer has a mechanical material feed. Indoor enclosureless dust collectors shall NOT have abrasive planers having mechanical feeds per 8.2.2.6.1.6. (7)(B):"The collector is not used on sanders, molders, or abrasive planers having mechanical material feeds through the machine"
AttentionDust collector falls under scope of NFPA 664. Dust collection system shall be demonstrated to meet these standards as applicable. Dust collector ductwork shall be shown on mechanical plans. Dust collector appears to have a flow rate range of 1,500 CFM through 3,000 CFM.
DisapprovedPlease demonstrate how sequence of operations meet the requirements of 2017 NFPA 664 8.2.2.2 Please provide the sequence of operation and how it will be consistently practiced; NOTE: 8.2.2.2 does REQUIRE the use of interlocks to ensure proper start up and shutdown operations.


 