RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

SLIM CHICKENS
01864 DEMOCRACY PT

Review DateStatusComment(s)
5/22/2020 DisapprovedIt appears this building will use CO2, but quantities not provided. If amount of CO2 is greater than 100 lbs, then a CO2 detection system shall be required in accordance with Section 5307 of the Colorado Springs Fire Code. If this system will be provided by the CO2 contractor, a deferred submittal may be requested. Please contact Stefan Manning at stefan.manning@coloradosprings.gov for deferred submittal information.
DisapprovedHAZARDOUS MATERIAL INVENTORY STATEMENT: All Processes/Operations, Materials/Chemicals indicated on the Hazardous Materials Triage form must be provided on a Hazardous Materials Inventory Statement (HMIS). An HMIS WAS NOT provided with the submittal. The HMIS shall include the following information: 1. Product name. 2. Component. 3. Chemical Abstract Service (CAS) number. 4. Location where stored or used. 5. Container size. 6. Hazard classification. 7. Amount in storage. 8. Amount in use-closed systems. 9. Amount in use-open systems.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com