RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

DERMATOLOGY CLINIC SUITE 150
02060 BRIARGATE PKWY

Review DateStatusComment(s)
2/26/2020 FYICHEMICAL INVENTORY, AS DECLARED Class IB Flammable Liquids - 7 gal total Reagent alcohol - Max storage amount - 4 gal (bought by the case) Eosin - 4 liters total, 1 liter containers Methanol - 1 gal container, 2 gal purchased at a time.
FYICONTROL AREAS, AS SHOWN ON THIS SUBMITTAL ARE AS FOLLOWS Entire Building
AttentionEXCEEDS PERMIT QUANTITIES; ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT REQUIRED. COLLECT REQUIRED INFORMATION FOR ANNUAL PERMITTING. Flammable liquids > 5 gal
AttentionINSPECTION REQUIRED. An inspection of this hazardous materials installation/process is required prior to final Certificate of Occupancy/occupancy of the building/commencement of hazardous materials operations. To schedule the hazardous materials inspection, please call 719-385-5978 and follow prompts to schedule the inspection. Please have the plan review number ready before calling.
IStorage is indicated in Flammable Liquid Storage Cabinets. These cabinets shall meet the requirements of 5704.3.2. 5704.3.2.1 Design and construction of storage cabinets. Design and construction of liquid storage cabinets shall be in accordance with Sections 5704.3.2.1.1 through 5704.3.2.1.4. 5704.3.2.1.1 Materials. Cabinets shall be listed in accordance with UL 1275, or constructed of approved wood or metal in accordance with the following: 1. Unlisted metal cabinets shall be constructed of steel having a thickness of not less than 0.044 inch (1.12 mm) (18 gage). The cabinet, including the door, shall be double walled with 1 1/2 -inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. 2. Unlisted wooden cabinets, including doors, shall be constructed of not less than 1-inch (25 mm) exterior grade plywood. Joints shall be rabbeted and shall be fastened in two directions with wood screws. Door hinges shall be of steel or brass. Cabinets shall be painted with an intumescent-type paint. 5704.3.2.1.2 Labeling. Cabinets shall be provided with a conspicuous label in red letters on contrasting background that reads: FLAMMABLE#KEEP FIRE AWAY. 5704.3.2.1.3 Doors. Doors shall be well fitted, self-closing and equipped with a three-point latch. 5704.3.2.1.4 Bottom. The bottom of the cabinet shall be liquid tight to a height of not less than 2 inches (51 mm). 5704.3.2.2 Capacity. The combined total quantity of liquids in a cabinet shall not exceed 120 gallons (454 L)


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version