RSS | Advanced Search | Site Map | Text Size a- A+
City of Colorado Springs
We Create Community

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

KIDS ROCK PEDIATRIC DENTISTRY
04515 BROADMOOR BLUFFS DR

Review DateStatusComment(s)
3/24/2020 I2015 IFC - ONE-HOUR EXTERIOR ROOMS. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both, with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have not less than one exterior wall that is provided with not less than two nonclosable louvered vents. Each vent shall have a minimum free opening area of 24 square inches (155 cm 2) for each 1,000 cubic feet (28 m 3) at normal temperature and pressure (NTP) of gas stored in the room and shall be not less than 72 square inches (465 cm 2) in aggregate free opening area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with not less than one automatic sprinkler to provide container cooling in case of fire. (2015 IFC ?5306.2.1) 1. 72 square inches aggregate met, total quantity of gases is 1480 scf, which would require each louver to be 24 square inches, 36 square inches provided. vent dimensions acceptable. 2. Per sheet P2, sprinkler head provided, inspector to verify sprinkler head is installed in closet.
Attention2015 IFC - MEDICAL GAS SYSTEMS. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall be installed in accordance with NFPA 99 and the general provisions of this chapter. Existing medical gas systems shall be maintained in accordance with the maintenance, inspection and testing provisions of NFPA 99 for medical gas systems. (2015 IFC ?5306.5) 1. Updated medical gas plans indicate the system will be designed as a Category 2 dental gas system. 2. Letter from dentist indicates highest level of sedation will be moderate sedation, which is acceptable.
AttentionCHEMICAL INVENTORY, AS DECLARED OXIDIZING GASES - 1480 scf Oxygen - 2 x 250 scf = 500 scf Nitrous Oxide - 2 x 56 lbs = 224 lbs = 980 scf Updated HMIS shows amounts of oxidizing gas < 1500 scf, no H occupancy required.
AttentionEXCEEDS PERMIT QUANTITIES; ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT REQUIRED. COLLECT REQUIRED INFORMATION FOR ANNUAL PERMITTING.
AttentionHAMMERS: The information from this permit application must be entered into the HAMMERS program and added to the facilities hazardous materials information. Visit the following link: https://hammers.springsgov.com/ to add the information to the facility.
AttentionPer comment response, medical gas alarm location is "highest traffic area of properly trained staff and is located at a central location to the rooms using the gas".
AttentionINSPECTION REQUIRED. An inspection of this hazardous materials installation/process is required prior to final Certificate of Occupancy/occupancy of the building/commencement of hazardous materials operations. To schedule the hazardous materials inspection, please call 719-385-5978 and follow prompts to schedule the inspection. Please have the plan review number ready before calling.
FYIMED GAS INSPECTIONS. Medical Gas system piping installation requires MULTIPLE INSPECTIONS by the CSFD due to installation requirements and procedures. ALL PORTIONS OF PIPING SYSTEMS SHALL REQUIRE INSPECTION; no piping shall be sealed or concealed prior to inspection. Contact the CSFD Office of the Fire Marshal at 385-5978 for an inspection schedule for this project. All paperwork, documentation, installer/verifier certifications, and needed test equipment shall be available upon Inspector's request.
FYIGENERAL. Medical gas systems shall be installed and inspected by credentialed American Society of Sanitary Engineering (ASSE) 6010 medical gas system installers, ASSE 6015 bulk medical gas system installers, ASSE 6020 medical gas system inspectors, and ASSE 6030 medical gas verifiers. Contractor shall be responsible for compliance with all local, state or federal codes, standards, and appropriate industry practices. (2015 IFC ?5306.1)
2/12/2020 Disapproved2015 IFC - ONE-HOUR EXTERIOR ROOMS. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the International Building Code, or both, with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have not less than one exterior wall that is provided with not less than two nonclosable louvered vents. Each vent shall have a minimum free opening area of 24 square inches (155 cm 2) for each 1,000 cubic feet (28 m 3) at normal temperature and pressure (NTP) of gas stored in the room and shall be not less than 72 square inches (465 cm 2) in aggregate free opening area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with not less than one automatic sprinkler to provide container cooling in case of fire. (2015 IFC ?5306.2.1) 1. 72 square inches aggregate met but total quantity of gases is 2614 scf, which would require each louver to be 48 square inches, not 36 square inches. 2. Additionally, the sprinkler head in the closet is missing. Please provide a sprinkler head in accordance with 2015 5306.2.1 exception.
AttentionINSPECTION REQUIRED. An inspection of this hazardous materials installation/process is required prior to final Certificate of Occupancy/occupancy of the building/commencement of hazardous materials operations. To schedule the hazardous materials inspection, please call 719-385-5978 and follow prompts to schedule the inspection. Please have the plan review number ready before calling.
FYICHEMICAL INVENTORY, AS DECLARED OXIDIZING GASES - 2614 scf Oxygen - 4 x 200 scf = 800 scf Nitrous Oxide - 4 x 56 lbs = 224 lbs = 1814 scf
AttentionEXCEEDS PERMIT QUANTITIES; ANNUAL HAZARDOUS MATERIALS OPERATIONAL PERMIT REQUIRED. COLLECT REQUIRED INFORMATION FOR ANNUAL PERMITTING.
FYICONTROL AREAS, AS SHOWN ON THIS SUBMITTAL ARE AS FOLLOWS
DisapprovedMedical gas alarm panel shown in the rear staff area. This does not appear to be an area that is constantly supervised; please relocate panel to an area where it will be constantly supervised (ie, reception area, etc).
DisapprovedTHE CHEMICAL INVENTORY, AS DECLARED, EXCEEDS THE ALLOWABLE THRESHOLDS FOR OXIDIZING GASES AS DEFINED BY 2015 IFC TABLE 5003.1.1(1) AND/OR 5003.1.1(2). YOU WILL BE REQUIRED TO RESUBMIT YOUR PLANS TO THE PPRBD FOR A RE-CLASSIFICATION OF THE OCCUPANCY TYPE IN WHICH THIS/THESE CHEMICAL TYPE(S) ARE USED AND/OR STORED, TO AN H3 PER THESE TABLES. NOTE THAT APPROPRIATE REVISIONS SHALL BE MADE AS REQUIRED BY THE BUILDING CODE FOR THIS NEW TYPE OF OCCUPANCY CLASSIFICATION. Please either clarify the amounts and storage locations of the gases to verify total amounts are 2,614 scf. If they are correct, an H-3 occupancy is required for the storage and use of the gases; alternatively the amounts shall be reduced to less than or equal to 1,500 scf.
Disapproved2015 IFC - MEDICAL GAS SYSTEMS. Medical gas systems including, but not limited to, distribution piping, supply manifolds, connections, pressure regulators and relief devices and valves, shall be installed in accordance with NFPA 99 and the general provisions of this chapter. Existing medical gas systems shall be maintained in accordance with the maintenance, inspection and testing provisions of NFPA 99 for medical gas systems. (2015 IFC ?5306.5) 1. Category indicated appears to be a Category 3 Dental System. Per 2018 NFPA 99, Category 3 dental systems are not allowed to have medical gases (15.1.2.). Please remove medical gases OR change category to Category 1 or 2. 2. Please provide a letter from the dentist in charge that indicates the highest level of sedation provided to the patients (minimal, moderate, deep sedation, general anesthesia). Note that Category 2 systems are allowed at most Moderate and Category 3 at most minimal sedation.


 

Contact Us: Email Us - Call: 385-CITY (719-385-2489) - RSS - Privacy, Linking and ADA Policies - designed, developed by projecta.com

printer friendly version Printer friendly version