NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

SAP AMERICA COS02 DATA CENTER
02345 WINDSWEPT VW

Review DateStatusComment(s)
2/28/2020 FYI*****(STANDARD COMMENT) This project is: SAP, 2345 Windswept This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****DESIGNER/INSTALLER INFORMATION Fire Alarm system was designed by: ETG Fire Fire alarm system is being installed by: SAME
FYIADDITIONS AND REMODELS TO EXISTING SYSTEMS: Existing systems shall comply with current codes and standards for all areas occupied by the tenant, not just the area of remodel.
FYI*****Scope of Work: Add VESDA protection to return air grilles - these detectors are not associated with any clean agent extinguishing system.
FYILICENSED INSTALLER/SERVICE TECHNICIAN An On-Site Installer/Service Technician shall supervise all on-site work on any fire protection system. This On-Site Installer shall have a current Installer Certificate (RBD Wallet Card), on his/her person, while on the job site.
FYICOMPLETION DOCUMENTS AND DOCUMENT CABINET: The following documents/records shall be provided in a DOCUMENT CABINET: 1. Owner's manual and manufacturer's published instructions for all system equipment 2. Record/As-Built drawings 3. Completed/Updated Record of Completion 4. For software based systems, record copy of site-specific software 5. Certificate of Installation A DOCUMENT CABINET SHALL BE PROVIDED FOR ALL NEW SYSTEM INSTALLATIONS! NFPA 72: 7.5 and 7.7
FYIPRE-TEST REQUIREMENT: Before requesting final approval of the installation, the installing contractor shall furnish a written statement that the system has been installed in accordance with approved plans and testing in accordance with the manufacturer's published instructions and the appropriate NFPA requirements. (10.18.1.3) CSFD requires a 100% pre-test - Evidence may be documented on the Record of Completion.
FYIACCEPTANCE TESTING: At the time of this inspection the Fire Inspector will expect ALL devices involved in this fire alarm project to be tested. The installer should be aware of the fact that in a larger facility there may be a need to isolate the fire alarm system to only the area being tested. The alarm installer is to insure that building owner and/or manager and the General Contractor has been informed of the test criteria, time and date of the test, and have given their approval. Acceptance testing shall be completed in accordance with Chapter 14 of NFPA 72
AttentionROUGH-IN PERMIT AND INSPECTIONS: All Fire Alarm systems wiring installed within the City of Colorado Springs must be inspected by the Pikes Peak Regional Building Department PRIOR TO the Fire Final on the system. This will require the installing contractor to obtain a Rough-In Permit issued by the Regional Building Department. Please call RBD at 327-2880 for additional information on how to obtain this permit.
FYI*****SCHEDULING INSPECTIONS Please call 719-385-5982 Extension 2 to schedule all construction related inspection activities. Due to the dynamic nature of inspectors schedules, PLEASE call your inspection requests in with ample time to allow scheduling. When calling, please have your complete CSFD plan review number(s) ready for each inspection request. ( i.e. 2013-1234 - HS-1) The CSFD Approved sets of plans are to be on site for all inspections.
FYIREVIEWS: Colorado Springs Fire Department plan reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirements are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the adopted fire code requirements, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)"
FYIAS-BUILT PLANS All deviations from approved plans shall be documented and submitted to CSFD for archival. Reviews will not be conducted on as-builts, as these field changes are often verified as compliant by the fire inspectors. All as-built plans shall be conspicuously marked as such. Any changes requiring approval prior to Final shall be submitted as a REVISION.
FYIDEW REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Doreen "Dee" Withee, PE Fire Protection Engineer II, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7361 dwithee@springsgov.com
2/3/2020 FYI*****(STANDARD COMMENT) This project is: SAP Americas, Inc COS02 Data Center, 2345 Windswept Vw: Fire Alarm Only This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****DESIGNER/INSTALLER INFORMATION Fire Alarm system was designed by: ETG Fire Fire alarm system is being installed by: ETG Fire
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Plan label of plans still does not match the scope of work or work notes noted on plans. Why are you labeling plans claen agent fire suppression shop drawings when only fire alarm work is being performed? 2. Is the new vesda detection interconnected to the clean agent suppression systems in the UPS rooms? If so, show interconnection in your sequence of operation to show when vesda will release clean agent system. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYICORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
AttentionTHE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYICLT REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Wyman "Chip" Taylor II, PE Fire Protection Engineer I Colorado Springs Fire Department Division of the Fire Marshal 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7303 wtaylor@springsgov.com
1/10/2020 FYI*****(STANDARD COMMENT) This project is: SAP Americas, Inc COS02 Data Center, 2345 Windswept Vw: Fire Alarm Only This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Plans are unclear as to what the scope of work is: - Plans are titled Clean Agent Fire Suppression System - Integration note states the clean agent calculations are in the cut sheets - the drawings don't reflect any clean agent components - no nozzles, tanks, piping, etc are given. and there are no clean agent calculations provided. - The Scope of Work and General Notes further confuse the situation as to what these plans are really for. It appears the plans are just for VESDA. Is this accurate? 2. Plans state Siemens will be installing all detection, including that for the clean agent system, however Siemens is not identified as the installing contactor for this scope fo work - which appears to be VESDA for the actuation of a clean agent system yet to be submitted. If anyone other than ETG Fire is installing this scope of work, they must be declared as such on the drawings and the RME must sign the cover sheet of the drawings. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Disapproved(STANDARD COMMENT) CONTRACTOR LICENSING. Our records indicate the license for this Fire Alarm Contractor is not current for the following reasons: --XXX---Liability Insurance Expired --XXX---Worker's Compensation Insurance Expired Please contact the Contractor Licensing Office of the Regional Building Department at 719-327-2887 to correct this problem.
FYICORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
AttentionTHE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYIJAH REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Jeff Hanenberg Senior Fire Code Inspector 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7359 jhanenberg@springsgov.com
12/13/2019 FYI***** WORK AT RISK On ---12/13/19-- approval was granted by --FPE WITHEE--- for work to begin by --ETG FIRE---without approved plans or permits. Any changes or modifications based upon plan review will be required to be completed. No inspections will be conducted without approved plans and permits.
11/18/2019 ApprovedPlace holder for AL-2 submittal


 